Condensate Return Systems: Seriously Useful Tips | RasMech
Condensate return systems are an often-overlooked part of a boiler system that allow you to recover valuable BTUs within your system. The sole purpose of a condensate return system is to collect condensate from different points in the system and return it to the boiler.
Why Worry About Condensate Returns?
Condensate has already been run through the boiler system once, which means there are a few benefits to using it over make-up water. For one, condensate has already gone through the chemical treatment process. This means returning this condensate to the feedwater tank or deaerator reduces the total dissolved solids (TDS) in the system. This means less chemical treatment is necessary and also can reduce blowdown losses.
The second benefit of using condensate returns is that they can increase the temperature of water heading into the boiler. The returns can be added to a feedwater tank and mixed with feedwater before entering the boiler. Hot condensate helps to reduce the heating load on a boiler, because it is easier to heat up hot water compared to cold feedwater. So not only does returning treated water reduce chemical requirements, but it also saves energy.
The third benefit of a condensate return system is it can reduce the amount of make-up water needed. When more condensate is returned that means there is less make up water needed to satisfy the boilers needs. This will ultimately create a savings on water use.
How To Improve Your Condensate Return Systems
Steam Traps Surveys
Condensate is discharged from equipment through steam traps. A steam trap simply allows condensate (condensed steam aka water) to pass while holding back (or trapping) steam. This ensures the steam that has yet to give up its energy stays in the system while the condensate gets removed.
As you can imagine, a malfunctioning or incorrectly sized steam trap can wreak havoc on your condensate return system. A steam trap that has gone bad may stick open or closed. As one of the few moving parts in your steam system, it is important to perform regular steam trap surveys . By ensuring steam traps are sized appropriately and operating correctly you can keep your condensate return system operating efficiently.
Note: High pressure traps should be tested quarterly.
Capture Flash Steam
After the condensate passes through a steam trap, a pressure change occurs. This causes some of the condensate to turn into flash steam. This It is another area where many companies can be losing money. If this flash steam is vented to the atmosphere, you are losing the valuable BTUs it contains. Instead, collect the steam in a flash vessel and use it for heating somewhere in the system. Be sure to also recover any condensate created when the flash steam gives up its energy and use it as well.
Spot Leaks and Corrosion
Condensate piping has to deal with a higher concentration of carbonic acid than the rest of the system. This is due to CO2 more easily dissolving in the cooling condensate. This can lead to steel corrosion which can eventually lead to leaks. Monitor your system for leaks and fix any that are found immediately to ensure savings isn’t sneaking out of your pipes.
Insulate Your Piping
According to the US Department of Energy : “Insulation can typically reduce energy losses by 90% and help ensure proper steam pressure on plant equipment. Any surface over 120 °F should be insulated, including boiler surfaces, steam and condensate return piping, and fittings.”
The better you are able to help condensate retain its heat, the more efficient your system will be. That is why insulation is no-brainer. It allows that condensate to maintain its heat for longer which results in less work for the boiler and ultimately saves you money.
Go through your entire system and make sure all piping is insulated. Fix any uninsulated areas to ensure you’re not losing massive amounts of heat as the condensate returns.
Contaminated Returns
In some instances, there may be a risk of contamination if condensate is returned to the boiler. If contaminated with corrosive liquids for example, it is unsuitable for boiler feedwater. This is because of the dangers of foaming, scaling, and corrosion.
Condensate contamination detection equipment can detect changes in conductivity in the condensate. When a change from the desired conductivity occurs, the sensors recognize that the condensate is contaminated. A controller then signals a dump valve to open. This allows condensate to flow to the drain or an economizer, instead of back to the boiler.
US DEPARTMENT OF ENERGY’S EXAMPLE
Consider a steam system that returns an additional 10,000 pounds per hour (lb/ hr) of condensate at 180 °F after distribution modifications. Assume this system operates 8,000 hours annually with an average boiler efficiency of 80%, and makeup water temperature of 55 °F. The water and sewage costs for the plant are $0.002 per gallon ($/gal), and the water treatment cost is $0.002/gal. The fuel cost is $8.00 per million Btu ($8.00/MMBtu). Assuming a 12% flash steam loss, * calculate overall savings.
ANNUAL WATER, SEWAGE, & CHEMICALS SAVINGS
= (1 — Flash Steam Fraction) x (Condensate Load, lb/hr) x Annual Operating Hours x (Total Water Costs, $/gal)/ (Water Density, lb/gal)
= (1–0.12) x 10,000 x 8,000 x $0.004 / 8.34
Annual Water, Sewage, & Chemicals Savings = $33,760
ANNUAL FUEL SAVINGS
= (1 — Flash Steam Fraction) x (Condensate Load, lb/hr) x Annual Operating Hours x (Makeup Water Temperature Rise, °F) x (Fuel Cost, $/MMBtu) x (Heat Capacity of Makeup Water, Btu/lb-°F)/ (Boiler Efficiency x 106 Btu/MMBtu)
= (1–0.12) x 10,000 x 8,000 x (180–55) x $8.00 x 1 / (0.80 x 106)
Annual Fuel Savings = $88,000
TOTAL ANNUAL SAVINGS DUE TO RETURN OF AN ADDITIONAL 10,000 LB/HR OF CONDENSATE
= $33,760 + $88,000
Total Annual Savings= $121,760
See the US Department Of Energy Tips Sheet Here
WE CAN HELP!
Talk to the condensate return systems experts. Whether you are working with a vented-to-atmosphere or a pressurized condensate recovery system we can help. Call us at 1–800–237–314 or simply contact us online.
Originally published at https://www.rasmech.com on June 29, 2021.